Technical Specifications |
|
The following tables summarise the technical parameters for the various input modules which can be supplied for use with the NetPod instrumentation. The specifications shown for the strain gauge interfaces are worst case and supplied units should operate above the results displayed in the table |

|
Specifications |
|
High Resolution |
|
Low Resolution |
|
Fast card |
|
CMMR |
|
160 dB |
|
160 dB |
|
160 dB |
|
Sample Rate |
|
0.1 - 2 KHz |
|
0.1 - 60 Hz |
|
0.1 - 78 KHz |
|
Isolation |
|
1500V RMS |
|
1500V RMS |
|
Dynamic Range |
|
150 dB |
|
96 dB |
|
Signal/Noise |
|
See Note 1 |
|
> 88 dB |
|
> 88 dB |
|
Gain Accuracy |
|
0.1 % |
|
0.1% |
|
0.1% |
|
Settling Time |
|
2 ms |
|
65 ms |
|
0.03 ms |
|
Input Range: V1 |
|
± 5.0 V |
|
± 2.5 V |
|
V2 |
|
V3 |
|
V4 |
|
± 50 V |
|
±25 V |
|
Resolution: V1 |
|
V2 |
|
V3 |
|
V4 |
|
0.6 mV |
|
80 mV |
|
2.0 mV |
|
Input Offset: V1 |
|
V2 |
|
V3 |
|
± 1 mV/°C |
|
± 1 mV/°C |
|
Stability: V1 |
|
V2 |
|
V3 |
|
10 ppm/°C |
|
20 ppm/°C |
|
15 ppm/°C |
|
Input V1 |
|
V3 |
|
V4 |
|
2 MW |
|
2 MW |
|
20 MW |
|
Overload |
|
250 V RMS |
|
250 V RMS |
|
250 V RMS |
|
Converter Type |
|
Sigma Delta |
|
Gain |
|
1,2,4,8,16 note 2 |
|
1,2,32, 128 |
|
1 |
|
Lineraity |
|
0.0015 % |
|
0.0015% |
|
0.005% |
|
Ethernet Specifications |
|
Transmion - 10Mbps baseband |
|
Maximum segment length per UTP drop cable is 100 metres |
|
10BaseT networks are easily upgradeable for 100BaseT and GigaStream operations |
|
Serial Port |
|
5 wire multi-instrument configuration |
|
Transmission speed 9600 baud Typical |
|
Poll rate 100 ms |
|
9600 baud transmission speed - adjustable |

|
Current Input |
|
± 80 mA, 0-20 mA |
|
± 80 mA, 0-20 mA |


|
Note 1 (range V1) |
|
16 |
|
Details for interface cards NPAI24-V1H1 NPAI24-V2H1 NPAI24-V3H1 |
|
Table 1 |